Open Access

Table 4

Power flow calculation comparison of P-model, S-model and ATP-model.

Tap position The sending end power flow after compensation/MVA
P-model S-model ATP-model Relative errors
Active power based on P-model Reactive power based on P-model Active power based on S-model Reactive power based on S-model
(0, 0) 283.20 + j30.84 283.23 + j30.73 282.19 + j30.97 0.357% 0.419% 0.368% 0.775%
(5, 0) 323.27 + j147.28 323.36 + j146.11 321.17 + j148.12 0.653% 0.567% 0.682% 1.35%
(5, 5) 423.30 + j163.99 423.53 + j162.73 418.92 + j164.84 1.04% 0.515% 1.10% 1.28%
(0, 5) 387.18 + j48.96 387.36 + j48.64 384.71 + j49.25 0.642% 0.588% 0.688% 1.23%
(−5, 5) 347.55 − j50.62 347.69 − j51.06 343.92 − j50.32 1.05% 0.596% 1.09% 1.47%
(−5, 0) 241.01 − j69.86 241.99 − j70.40 239.72 − j69.36 0.534% 0.721% 0.946% 1.49%
(−5, −5) 135.21 − j65.55 135.54 − j66.04 133.82 − j64.85 1.03% 1.07% 1.28% 1.83%
(0, −5) 179.16 + j34.59 179.55 + j34.32 178.18 + j34.84 0.550% 0.718% 0.769% 1.49%
(5, −5) 222.37 + j150.10 222.42 + j149.51 220.75 + j151.42 0.734% 0.872% 0.757% 1.26%