Table 3

Summary of heat sources and heat flows in a typical two-phase cooled data center [18].

Parameter Value
Coolant supply evaporator 60 °C saturated liquid (standard), 70–75 °C (maximum)
Evaporator outlet coolant mass 62 °C 30% by mass (standard) 75–80 °C (maximum)
Vapor compressor outlet coolant temperature 90 °C
Condenser coolant inlet 30 °C
Condenser coolant outlet 90 °C