Results with P and PQV buses for IEEE 33-bus RDS.

Items Results with new multi-objective function
Case 1 Case 2 Case 3 Case 4 Case 5
Open switches 33, 34, 35, 36, 37 7, 9, 14, 28, 32 7, 9, 14, 17, 28 14, 20, 28, 30, 35 14, 20, 32, 35, 37
DG MW @ bus 1.94446 @ 25 2.80449 @ 9 3.0190 @ 7
APL (kW) 151.25 109.55 49.27 84.45 77.32
QPL (kVAr) 102.81 84.95 42.79 65.58 60.95
λmax 2.95 4.75 6.93 7.25 6.67
QLI 3.5874 3.61982 3.68286 3.7184 3.7147
APLR% 25.38 45.948 75.688 58.33 61.85
QPLR% 23.92 37.132 68.330 51.47 54.90
Vmin @ bus 0.9300 @ 18 0.9477 @ 33 0.9644 @ 17 0.9909 @ 25 0.9851 @ 25
Vmax @ bus 1 @ 1 1 @ 1 1.008 @ 25 1.025@6 1.015 @ 7