Table 4
Identification of inertial constants of power systems with different new energy penetration.
New energy unit serial number | Penetration rate/% | Reference value/s | Non−recursive identification results |
Recursive identification results |
||
---|---|---|---|---|---|---|
Identification value/s | Error/% | Identification value/s | Error/% | |||
None | 0.00 | 4.577 | 4.626 | 1.07 | 4.833 | 5.59 |
G09 | 13.52 | 4.375 | 4.515 | 3.18 | 4.467 | 2.10 |
G07, G09 | 22.64 | 4.221 | 4.284 | 1.48 | 4.171 | −1.19 |
G05, G06, G07, G09 | 41.49 | 3.865 | 3.683 | −4.70 | 3.559 | −7.93 |
Current usage metrics show cumulative count of Article Views (full-text article views including HTML views, PDF and ePub downloads, according to the available data) and Abstracts Views on Vision4Press platform.
Data correspond to usage on the plateform after 2015. The current usage metrics is available 48-96 hours after online publication and is updated daily on week days.